[Home]

[Report Table of Contents]

March 2003 Off-Post Quarterly Groundwater Monitoring Report

Appendix C - Pre- and Post-GAC Sample Comparisons

Wells LS-6, LS-7, RFR-10, RFR-11, LS-2/LS-3 and OFR-3

LS-2/LS-3

LS-6

 

PCE (�g/L)

TCE (�g/L)

 

PCE (�g/L)

TCE (�g/L)

Date

Pre

Post

Pre

Post

Date

Pre

Post

Pre

Post

03/18/02

2.9/1.3

NA

0.29/0.63

NA

08/15/01

GAC UNIT INSTALLED

04/2002

GAC UNIT INSTALLED

08/30/01

5.7

ND

0.57

ND

04/11/02

0.82/1.53

ND

ND/ND

ND

09/19/01

6.7

ND

0.35

ND

06/12/02

2.22/1.06

NA

0.31/0.20

NA

09/27/01

20.0

NA

0.38

NA

09/17/02

2.62/2.9

ND

0.17/0.21

ND

12/18/01

1.97

ND

ND

ND

03/12/03

4.25/3.99

ND

0.30/0.35

ND

03/18/02

2.7

ND

0.2

ND

 

 

 

 

 

09/16/02

1.58

ND

0.1

ND

 

 

 

 

 

03/12/03

4.19

ND

0.21

ND

 

LS-7

OFR-3

 

PCE (�g/L)

TCE (�g/L)

 

PCE (�g/L)

TCE (�g/L)

Date

Pre

Post

Pre

Post

Date

Pre

Post

Pre

Post

08/07/01

GAC UNIT INSTALLED

03/19/02

12.15

NA

5.65

NA

08/08/01

NA

ND

NA

ND

04/16/02

9.38

NA

3.77

NA

08/30/01

1.1

NA

ND

NA

4/30/02

GAC UNIT INSTALLED

09/19/01

4.5

ND

0.81

ND

04/30/02

NA

ND

NA

ND

09/27/01

6.6

NA

0.68

NA

06/11/02

10.22

NA

6.24

NA

12/18/01

1.4

ND

ND

ND

09/16/02

2.96

ND

2.59

ND

03/18/02

2.7

ND

0.24

ND

03/12/03

2.81

ND

3.25

ND

09/16/02

2.41

ND

0.34

ND

 

 

 

 

 

03/12/03

4.01

ND

0.41

ND

 

 

 

 

 

 

RFR-10

RFR-11

 

PCE (�g/L)

TCE (g/L)

 

PCE (g/L)

TCE (g/L)

Date

Pre

Post

Pre

Post

Date

Pre

Post

Pre

Post

10/09/01

GAC UNIT INSTALLED

10/04/01

16.0

NA

0.35

NA

10/12/01

20.89

ND

8.21

ND

10/12/01

16.73

NA

0.58

NA

12/17/01

9.02

ND

5.85

ND

10/16/01

GAC UNIT INSTALLED

03/18/02

4.5

ND

2.2

ND

10/25/01

NA

ND

NA

ND

09/16/02

9.19

ND

4.84

ND

12/17/01

12.44

ND

ND

ND

03/12/03

13.88

ND

8.37

ND

03/19/02

5.71

ND

1.05

ND

 

 

 

 

 

09/16/02

8.44

ND

0.67

ND

 

 

 

 

 

03/12/03

10.02

0.07F

0.12

ND

NA � not applicable (post-GAC not sampled during this event)