[Home]

[Table of Contents]

March 2002 Off-Post Quarterly Groundwater Monitoring Report

Table 5.1 - Pre- and Post-GAC Comparison for Wells LS-6, LS-7, RFR-10, and RFR-11

LS-6

LS-7

 

PCE (ug/L)

TCE (ug/L)

 

PCE (ug/L)

TCE (ug/L)

Date

Pre

Post

Pre

Post

Date

Pre

Post

Pre

Post

 

08/15/01

GAC UNIT INSTALLED

08/07/01

GAC UNIT INSTALLED

 

08/30/01

5.7

ND

0.57

ND

08/08/01

NA

ND

NA

ND

 

09/19/01

6.7

ND

0.35

ND

08/30/01

1.1

NA

ND

NA

 

09/27/01

20.0

NA

0.38

NA

09/19/01

4.5

ND

0.81

ND

 

12/18/01

1.97

ND

ND

ND

09/27/01

6.6

NA

0.68

NA

 

03/18/02

2.7

ND

0.2

ND

12/18/01

1.4

ND

ND

ND

 

 

03/18/02

2.7

ND

0.24

ND

 

RFR-10

RFR-11

 

PCE (ug/L)

TCE (ug/L)

 

PCE (ug/L)

TCE (ug/L)

Date

Pre

Post

Pre

Post

Date

Pre

Post

Pre

Post

10/09/01

GAC UNIT INSTALLED

10/04/01

16.0

NA

0.35

NA

10/12/01

20.89

ND

8.21

ND

10/12/01

16.73

NA

0.58

NA

12/17/01

9.02

ND

5.85

ND

10/16/01

GAC UNIT INSTALLED

03/18/02

4.5

ND

2.2

ND

10/25/01

NA

ND

NA

ND

 

12/17/01

12.44

ND

ND

ND

03/19/02

5.71

ND

1.05

ND

NA � not applicable

ND � indicates analyte was not detected at or above the method detection limit.